| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 23+, 24- | |
| Rated voltage | 20 ... 30 V DC | |
| Rated current | approx. 130 mA | |
| Power dissipation | 2 W | |
| Power consumption | 2.5 W | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3 | |
| Input I | ||
| Input signal | 0/4 ... 20 mA | |
| Available voltage | ≥ 15 V at 20 mA | |
| Open circuit voltage/short-circuit current | 24 V / 33 mA | |
| Input resistance | 45 Ω (terminals 2, 3) | |
| Line fault detection | breakage I < 0.2 mA; short-circuit I > 22 mA | |